Mitsubishi Freqrol-Z024-UL Controler -Parameter Description
Parameter
|
No.
|
Parameter Description |
Setting Range |
Initial Setting |
|
1st
|
0
|
Torque Boost (manual) |
0-30% |
6% |
Function
|
1
|
Max. Frequency Limit |
0-120 Hz |
120 Hz |
"
|
2
|
Min. Frequency Limit |
0-60 Hz |
0 Hz |
"
|
3
|
V/F (base frequency) |
50-360 Hz |
60 Hz |
"
|
4
|
3-Speed Setting (high speed) |
0-360 Hz |
60 Hz |
"
|
5
|
3-Speed Setting (middle speed) |
0-360 Hz |
30 Hz |
"
|
6
|
3-Speed Setting (low speed) |
0-360 Hz |
10 Hz |
"
|
7
|
Acceleration Time |
0,0.1-3600 sec. |
5 sec. |
"
|
8
|
Deceleration Time |
0,0.1-3600 sec. |
5 sec. |
"
|
9
|
Motor Thermal Relay |
0-999.9 A |
(1) |
2nd
|
10
|
PWM Mode |
0-15, 20-33 |
3 |
Function
|
11
|
DC Dynamic Braking Time |
0-10 sec. |
0.5 sec. |
"
|
12
|
DC Dynamic Braking Voltage |
0-10 % |
8% |
"
|
13
|
Starting Frequency |
0.5-10 Hz |
0.5 Hz |
"
|
14
|
Applied Load Selection |
0,1,2,3,10,11,12,13 |
0 |
"
|
15
|
Jog Frequency |
0-360 Hz |
5 Hz |
"
|
16
|
Jog Acceleration/Deceleration Time |
0,0.1-3600 sec. |
.5 sec. |
"
|
17
|
2nd Acceleration/Deceleration Time |
0,0.1-3600 sec. |
9999 |
"
|
18
|
High Speed Maximum Frequency |
120-360 Hz |
120 Hz |
"
|
20
|
Frequency @ 10V Input Voltage |
1-360 Hz |
60 Hz |
"
|
21
|
Stall Prevention Level |
0-200 % |
150% |
" |
24
|
Multi-speed Setting 4 |
0-360 Hz, 9999 |
9999 |
"
|
25
|
Multi-speed Setting 5 |
0-360 Hz, 9999 |
9999 |
"
|
26
|
Multi-speed Setting 6 |
0-360 Hz, 9999 |
9999 |
"
|
27
|
Multi-speed Setting 7 |
0-360 Hz, 9999 |
9999 |
"
|
29
|
Acceleration/Deceleration Pattern Selection |
0,1,2 |
0 |
"
|
37
|
Speed Display |
0,1,2,4,6,8,10,11, to 9998 |
0 |
"
|
39
|
Frequency @ 20 mA Input |
1-360 Hz |
60 Hz |
"
|
42
|
Up-to-frequency Detection |
0-100 % |
10% |
"
|
43
|
Output Frequency Detection |
0.5-360 Hz |
6 Hz |
"
|
44
|
Output Frequency Detection @ Reverse |
0.5-360 Hz, 9999 |
9999 |
"
|
45
|
DC Dynamic Braking Frequency |
0-60 Hz |
3 Hz |
"
|
46
|
External Thermal Relay Input Selection |
0,1 |
0 |
"
|
47
|
2nd Deceleration Time |
0,0.1-3600 sec., 9999 |
9999 |
"
|
48
|
2nd Torque Boost |
0-30 %, 9999 |
9999 |
"
|
49
|
2nd V/F (base frequency) |
50-360 Hz, 9999 |
9999 |
"
|
50
|
Retry Selection |
0,1,2,3 |
0 |
"
|
51
|
Retry Count @ Alarm Occurrence |
0,1 to 10, 101 to 110 |
0 |
"
|
52
|
Retry Execution Wait Time |
0.01 to 360 sec. |
1 sec. |
"
|
53
|
Retry Execution Count Display Erase |
0 |
0 |
"
|
69
|
Set by the Manufacturer (DO NOT SET) |
*
|
*
|
"
|
70
|
FM Output Terminal Function Selection |
0, 1 |
0 |
"
|
72
|
Current Monitoring Output Gain |
0-200 % |
150% |
"
|
73
|
5V / 10V Input Selection |
0, 1 |
0 |
"
|
74
|
Current Input Selection |
0, 1 |
0 |
"
|
75
|
Reset Selection |
0, 1 |
0 |
"
|
76
|
Output Signal Selection |
0, 1, 2 |
0 |
"
|
77
|
Parameter Write Prohibition |
0, 1, 2 |
0 |
"
|
78
|
Reverse Rotation Prevention Selection |
0, 1, 2 |
0 |
"
|
79
|
Operation Mode Selection |
0, 1, 2, 11, 12 |
0 |
3 rd
|
C-1
|
Frequency Meter Calibration |
----- |
----- |
Function
|
C-2
|
Bais for Frequency Reference Voltage |
0-120 Hz |
0 Hz |
"
|
C-3
|
Gain for Frequency Reference Voltage |
1-360 Hz |
60 Hz |
"
|
C-4
|
Bais for Frequency Reference Voltage |
0-120 Hz |
0 Hz |
"
|
C-5
|
Gain for Frequency Reference Voltage |
1-360 Hz |
60 Hz |
Notes:
*1. Set values differ depending on inverter capacity.
1. For parameters marked with an asterisk, it is possible to change set values during operation in either PU-op or External mode. Pr.10 may only be changed while in PU-op mode. (Pr.77=0, initial setting) |
|
|
2. Minimum setting step |
|
|
|
* Frequency………………0.01 Hz. Note, if frequency is 100 Hz or higher, it is 0.1 Hz. |
|
* Time……………………0.1 seconds. Note, if 0 is entered, 0.04 seconds is set. |
|
* Current…………………0.1 A |
|
* %………………………1% |
3. The set value of 9999 indicates that "the function is active." |
|